| DC voltage range | 350/700 VDC | 
| Input voltage | 2*230 VAC (positive and negative poles separately fed by AC/DC converters) | 
| Grounding scheme applied on AC part (input) | TNS | 
| Grounding scheme applied on DC part (output) | Capacitive midpoint earthing | 
| Connection power | 6 kW | 
| Peak power 6 kW | 6 kW | 
| Galvanic isolation? | yes, through isolated AC/DC | 
| Ratio of peak to average consumed power | 
 | 
| Percentage of reused braking energy | no motors in the system | 
| Easy integration of renewable energies? | yes | 
| Power of the connected storage | 5.5 kW | 
| Energy of the connected storage | 
 | 
| Planning with the guideline is completed? | 
 | 
| UL/IEC-conform? | 
 | 
| Extension possible? | yes, additional loads, storage elements and renewables could be added to the grid | 
| Retrofit (brownfield) or greenfield? | greenfield | 
| Companies/partners involved | TU Delft | 
| Area | The Green Village - TU Delft | 
| Public power distributor involved? | no | 
| Further savings? | Solid-state circuit breakers protect the system: copper savings in the cables. Direct connection of solar panels through partial power converter to reduce losses up to factor 2 |