DC voltage range | 650-700 VDC |
Input voltage | 400 VAC |
Grounding scheme applied on AC part (input) | AC-TN-S-System |
Grounding scheme applied on DC part (output) | DC-TN-System with AC-side grounding |
Connection power | 86 kVA |
Peak power | 180 kVA |
Galvanic isolation? | no |
Easy integration of renewable energies? | DC coupled PV |
Power of the connected storage | 28 kW |
Energy of the connected storage | 55,2 kWh AC-Storage, to be integrated in DC |
Planning with the guideline is completed? | no |
UL/IEC-conform? | no |
Extension possible? | yes |
Retrofit (brownfield) or greenfield? | brownfield |
Companies/partners involved | EFA NRW, Fraunhofer IOSB-INA, Hadi-Plast, IANUS, Lenze, Stadtwerke Lemgo, Weidmüller, ZUG |
Area | 1,500 m2, partly public |
Public power distributor involved? | no |
Further savings? | from installed PV (51 kWp) |